10 hp single phase motor amps11/24/2023 ![]() Breaker shouldn't be used as a switch although many do. ![]() Posted 19:55 (#5172177 - in reply to #5171853) Subject: RE: Grain bin wiringĪssuming this is 230 volt 3 phase, The 7.5hp should have 45 amp breaker and 8 gauge THHN wire, you should have a disconnect no question. ![]() I would definatlly put a disconnect right next to the door. What size conduit will 6 and 8 fit in? Looking at NM-B since it's cheaper than running single strands Fan has starter switches so will direct wire Probably needs 6 gauge? Probably 20-30 feet from panel. Will 8 gauge hold it with a 40 amp breaker? Should I put a disconnect in or just use breaker in panel. Posted 17:54 (#5171853) Subject: Grain bin wiringħ.5 HP unload/sweep. Grain bin wiring Jump to page : 1 Now viewing page 1